Surge Tec Secondary Arresters

MacLean's Surge Tec® Arresters incorporate special features that make them stand above other Secondary Arresters and Transient Voltage Surge Suppressors (TVSS). These arresters use a patented (#5,502,612) fault withstand design along with replacement indication.

The arresters are available in 175 volt, 480 volt and 650 volt AC ratings for application on system voltages below 650 volts phase to ground and operate at frequencies between 48 and 62 Hz.The units come with 18 inch, #14 AWG solid copper wire leads and are designed to be mounted outdoors or indoors.

Description

FAULT WITHSTAND CAPABILITY - Surge Tec® secondary arresters' patented design achieves a fault withstand capability of 10kA rms without the use of any external fusing. This unique design has been tested at high current failure modes to verify its ability to withstand a failure without a violent fracture of its housing. Fault current is the full available current that the device conducts in the event it is short circuited by conducting a surge beyond the designed capability. This provides significant advantages in the area of secondary voltage protection.

REPLACEMENT INDICATION - A visual indication on the front label permits routine checks of the arrester's operational status. Indication windows on the label turn black if the arrester fails. The arrester should be replaced when any area of any window turns black.

Application:

  • MacLean's Surge Tec® arresters are classified for category B and C installations based on the diagram shown below.
  • The arresters are designed for repeated operation and continuous protection.
  • Surge arresters provide the path of least resistance to ground for surges on a system.
  • To provide the best protection, the lead wires should be kept as short as possible. When installed properly, they will divert lightning surges to ground very quickly.
  • Surge Tec® arresters offer the first line of defense for the entire electrical service and protect wiring, major appliances, pumps, and heating/air conditioning equipment.
  • For added protection to computers, MacLean Power Systems recommends a plug-in-strip type of device with lower clamping voltages as a second line of defense. This type of coordination provides excellent surge protection for the entire electric service.

THE ARRESTERS SHOULD BE INSTALLED BY A LICENSED ELECTRICIAN.

Links & PDFs

  • MacLean Power Guarantee - A one (1) year warranty is provided on all products manufactured.

 

Catalog Number Fig. Voltage Rating MCOV Poles Energy Cap. (Joules/Phase) Response Time (nsec.) Front-of-Wave Protection Level (kV Crest) 1.5kA 5.0kA 10kA Weight Oz. (Grams)
Z1-175-0 1 175 1 300 <5 1.21 .747 .954 1.271 14 [435]
Z1-480-0 2 480 1 500 <5 1.900 1.417 1.761 2.160 18 [560]
Z1-650-0 2 650 1 700 <5 2.48 2.009 2.439 2.850 19 [590]
Z2-175-0 1 175 2 300 <5 1.21 .747 .954 1.271 15 [466]
Z2-480-0 2 480 2 500 <5 1.900 1.417 1.761 2.160 19 [590]
Z2-650-0 2 650 2 700 <5 2.48 2.009 2.439 2.850 20 [622]
Z3-175-0 2 175 3 300 <5 1.21 .747 .954 1.271 18 [560]
Z3-480-0 2 480 3 500 <5 1.900 1.417 1.761 2.160 20 [622]
Z3-650-0 2 650 3 700 <5 2.48 2.009 2.439 2.850 21 [653]
Z3-650-2A 3 650 3 700 <5 2.48 2.009 2.439 2.85 21 (653)
Z2-175-0A 1 175 2 300 <5 1.21 0.747 0.954 1.271 15 (466)

 





Typical Wiring Connections


Maximum Phase-Phase/Phase-Ground Voltages

Fig. No. (Below)

Z1-175

Z2-175

Z3-175

Z1-480

Z2-480

Z3-480

Z1-650

Z2-650

Z3-650

3

175/NA

 

 

480/NA

 

 

650/NA

 

 

4

 

350/NA

 

 

960/NA

 

 

1300/NA

 

5

 

350/175

 

 

960/480

 

 

1300/650

 

6

 

 

303/175

 

 

831/480

 

 

1125/650

7

 

 

303/175

 

 

831/480

 

 

1125/650

8

 

175

 

 

480

 

 

650

 

9

 

 

175/101

 

 

480/277

 

 

650/375

10

 

 

175/101

 

 

480/277

 

 

630/375

* For severe duty applications, select arrester with next highest voltage rating.


Maximum Phase-Phase/Phase-Ground Voltages